Behaviour reference

IEC 61131-3 says what most operations give and leaves the rest to the implementer: what happens at the edges of a type, how text looks, what an error does. This part of the book says, for each operation iecf compiles, what it gives — the ordinary cases and every edge — and what the program is told when something is not as it should be.

Each choice is recorded with the vendors it was checked against in Implementer choices. This part is the reference for the results themselves.

Three outcomes

An operation in iecf either gives its result, or gives a result and flags it, or faults.

The taskThe program seesThe platform sees
Resultgoes onthe valuenothing
Flaggoes ona value, as the page for the operation saysctx->flag: the first flag’s code, POU and line, until the platform clears it
Faultstopsnothing more: the task returns at oncectx->fault: its code, POU and line; no task runs until a restart

A flag is for a result that is defined but probably not what the program wanted: an overflow that wrapped, a string cut to fit, a REAL that became infinite. The program carries on, as Siemens and Rockwell carry on with an error bit set; the platform can show the first flag to the user. A fault is for an operation that has no result to go on with: a division by zero, an index outside its array, a NULL reference dereferenced.

Some flagged conversions have no value to give: a REAL too large for an INT has no low bits to keep. Then the statement is left undone: an assignment keeps its target’s old value, an IF or CASE runs no branch, a FOR does not run, a WHILE or REPEAT ends (Conversions).

The codes

ctx->flag.code and ctx->fault.code hold an IECF_FAULT_* of runtime/iecf.h (The C output §5):

CodeNameKindWhen
1DIVISION_BY_ZEROfaultan integer, real or duration divided by zero
2OVERFLOWflagan integer, TIME, DATE or DT result outside its type, wrapped; an infinite real
3INDEXfaultan array index outside its bounds
4CONVERSIONflaga conversion to a type that cannot hold the value; text that is no literal of the type; a subrange store outside its bounds
5MUXfaultMUX’s K outside 0 .. n-1
6NEGATIVEfaulta negative shift or rotate count
7STRING_LENGTHflaga string cut to fit the variable it is stored in
8IMAGEfaultthe platform’s process image smaller than the program addresses
9NANflaga real result that is not a number
10STRING_POSITIONflaga string function’s length or position outside its string
11SFCflagan SFC step entered while still active; an action’s associations in conflict (SFC)
12NULLfaulta NULL reference dereferenced (References)

Reading the tables

The examples in this part are checked: CI compiles each row with iecf, runs it, and fails if the result or the flag is not what the row says (cargo run -p iecf-harness -- book). Each row is the statement r := Expression; with r of the row’s Type. A table that needs an extension says so above it, and its rows are built with that extension on (extensions).

  • Result is the value r holds afterwards, as an IEC literal; NaN, +inf and -inf for those reals; unchanged when the statement was left undone; — when the operation faulted.
  • Flag is flag NAME or fault NAME, raised by that statement, or — for neither.

A typed literal (INT#32767) is used where a plain one would be computed by the checker: 32767 + 1 is a constant 32768, which an INT cannot hold, and is refused before the program runs (E0020).