SFC

A PROGRAM or FUNCTION_BLOCK may be a Sequential Function Chart (Ed.3 6.7): steps, transitions between them, and actions associated with the steps. iecf compiles the textual form — STEP, TRANSITION, ACTION — which is also what a graphical editor writes. A POU is either a chart or statements, not both.

One scan

Each time the POU runs, in this order:

  1. Step times. Each active step’s T is the time since it was entered, in whole milliseconds, from the task’s clock.
  2. Action control. Each action’s qualifier logic — the standard’s ACTION_CONTROL — is evaluated with the steps active now: its Q (the action flag) and whether it runs (A).
  3. Actions. A BOOL variable used as an action takes Q. Action bodies run in two passes, as CODESYS and TwinCAT run them: first those that are ending (their final scan, a P1 or P0 pulse), then those whose Q is TRUE, each pass in source order. An action that is ending cannot overwrite what an active one writes.
  4. Transitions. Against the steps active when the scan began: a transition whose preceding steps are all active, and whose condition is TRUE, is cleared — its preceding steps left, then its following steps entered.

A step entered in this scan runs its actions from the next one: every step’s actions run at least once before it can be left (“the duration of a step activity can never be considered to be zero”, Ed.3 6.7.5). CODESYS and TwinCAT work the same way; matiec tests the transitions first. (Implementer choices)

Steps

S.X is TRUE while step S is active, S.T the time since it was entered; when S is left, S.T keeps its last value, and entering it again starts it at T#0s. Neither can be assigned (Ed.3 6.7.2). S.T stops at TIME’s largest value, after 24 days. The initial step is active from the start; its time starts at the first scan.

Actions and qualifiers

An action runs under the qualifiers of its active associations (Ed.3 Table 59), with final scan (Table 60, feature 1): once its Q falls, it runs one more time with Q FALSE, so it can tidy up. Inside the action, ACTION.Q tells which: IF NOT Fill.Q THEN valve := FALSE;.

QualifierThe action’s QRuns
N (or none)while the step is activewhile Q, and one final scan
Sfrom the step’s start, stored after ituntil an R, then one final scan
Rresets a stored action (S, SD, DS, SL) and overrides N—
L tfrom the step’s start, for at most twhile Q, and one final scan
D tafter t, if the step is still activewhile Q, and one final scan
Pfor one scan, on entrytwice: with Q, then its final scan
P1neveronce, on entry, Q FALSE
P0neveronce, on leaving, Q FALSE
SD tt after the step’s start, storeduntil an R, then one final scan
DS tafter t if the step is still active, then storeduntil an R, then one final scan
SL tfrom the step’s start, stored, for at most twhile Q, and one final scan

P runs twice. The standard’s action control gives every qualifier but P1 and P0 its final scan, P too (Ed.3 6.7.4.6, NOTE 3), and CODESYS documents that its P action is “executed exactly two times”. For an action that should run once on entry — counting entries — use P1.

The final scan and P0 follow a falling edge that happened: the standard’s figure draws them with F_TRIG, which would also fire on the very first scan; no vendor does that, and iecf does not.

Transitions and their priority

Of the transitions leaving the same active step, the first true one is cleared: those with (PRIORITY := n) by the lowest n (Ed.3 Table 61, 2b), then in source order (2a, as the leftmost branch first). The others wait. Transitions leaving different steps clear together, so a simultaneous divergence TO (S2, S3) activates both branches, and a convergence FROM (S2b, S3) waits for every one of its steps.

Errors

Ed.3 asks the system to treat these as errors. iecf flags them SFC (code 11) and goes on:

  • An “unsafe” chart: a step entered while it is still active (Ed.3 Figure 26 a). It stays active, once; its time goes on.
  • More than one time-related association active for one action (6.7.4.6 d): the last one’s duration is used.
  • SD while the action’s SL is stored, or SL while its SD is (6.7.4.6 d).

A chart that can lock up (“unreachable”, Figure 26 b) is the program’s own logic; nothing at run time can tell it from one that waits.

Restarts

A cold start, and a warm one, set every chart to its initial step. A FUNCTION_BLOCK instance kept whole across a warm start (RETAIN) keeps its steps, times and action states, as Ed.3 6.7.2 has it for a retentive instance.

Not yet: an indicator variable on an association (deprecated, Ed.3 Annex B), and steps and actions in the symbol table.