E0024: a VAR_CONFIG entry that does not fit the variable it names

A VAR_CONFIG entry names a variable inside a program instance and gives it an address, an initial value, or both (Ed.3 6.8.2):

  • the path names a variable, not just a program instance;
  • an address goes only to a variable declared AT %I*, %Q* or %M*, is in the same area (%Q* gets a %Q address), and is complete;
  • an initial value does not go to a VAR_TEMP, VAR_EXTERNAL, VAR_IN_OUT or CONSTANT variable.

The entry repeats the variable’s type; a different type is E0013.

VAR_CONFIG
  cpu.main.pump.coil AT %IX0.0 : BOOL;   (* E0024: coil is AT %Q* *)
  cpu.main.count AT %MW4 : INT;          (* E0024: count has no '*' address *)
  cpu.main.count : INT := 100;           (* fine: an initial value *)
END_VAR